نحوه پارامتر دهی به اینورترهای 400 
ردیف نحوه ریست        
      مقدار تنظیم شده  
1 P0003  User access level   3  
2 P0004  Parameter filter   0  
3 P0010  Commissioning parameter   30  
4 P0970  Factory reset   1  
نحوه پارامتر دهی
5 P0700  Selection of command source   2  Terminal  
6 P0701  Function of digital input 1   9 Fault acknowledge 
7 P0702  Function of digital input 2   12  Reverse  
8 P0703  Function of digital input 3   16  Fixed setpoint (Direct selection + ON)  
9 P0731  BI: Function of digital output 1   52.2  Drive running  
10 P0732  BI: Function of digital output 2   52.3  Drive fault active  
11 P0733  BI: Function of digital output 3   52.7  Drive warning active  
12 P1080  Min. frequency   35  
13 P1082  Max. frequency   50  
14 P1120  Ramp-up time   3  
15 P1121  Ramp-down time   3  
16 P1210  Automatic restart   0  Disabled  
17 P1237  Dynamic braking   2  10 % duty cycle